A Method of Fault Location Detection on Branched Power Transmission Lines


如何引用文章

全文:

开放存取 开放存取
受限制的访问 ##reader.subscriptionAccessGranted##
受限制的访问 订阅存取

详细

Using a method with different signal-to-noise ratios to search for a location of a fault location in branched power-transmission lines (PTLs) is considered in the work. A simulation model of a branched PTL is developed in the MATLAB software package. The relative error of fault location determination by changing the signal-to-noise ratio on the PTL and simulating different types of faults is studied in the simulation model. Three simulated pulses are used as the location signal: a single rectangular pulse, chirp signal, and Barker code with changing pulse width. It is revealed that choosing the location signal results in the maximum achievable accuracy of fault detection. Using the Barker code provides determination of fault location with an error of 0.2% and signal-to-noise ratio of more than 27 dB.

作者简介

R. Shagiev

Institute of Physics, Kazan Federal University

编辑信件的主要联系方式.
Email: journal-elektrotechnika@mail.ru
俄罗斯联邦, Kazan, 420008

A. Karpov

Institute of Physics, Kazan Federal University

Email: journal-elektrotechnika@mail.ru
俄罗斯联邦, Kazan, 420008

S. Kalabanov

Institute of Physics, Kazan Federal University

Email: journal-elektrotechnika@mail.ru
俄罗斯联邦, Kazan, 420008

补充文件

附件文件
动作
1. JATS XML

版权所有 © Allerton Press, Inc., 2019