A Method of Fault Location Detection on Branched Power Transmission Lines
- Authors: Shagiev R.I.1, Karpov A.V.1, Kalabanov S.A.1
-
Affiliations:
- Institute of Physics, Kazan Federal University
- Issue: Vol 90, No 2 (2019)
- Pages: 135-139
- Section: Article
- URL: https://journals.rcsi.science/1068-3712/article/view/231524
- DOI: https://doi.org/10.3103/S106837121902010X
- ID: 231524
Cite item
Abstract
Using a method with different signal-to-noise ratios to search for a location of a fault location in branched power-transmission lines (PTLs) is considered in the work. A simulation model of a branched PTL is developed in the MATLAB software package. The relative error of fault location determination by changing the signal-to-noise ratio on the PTL and simulating different types of faults is studied in the simulation model. Three simulated pulses are used as the location signal: a single rectangular pulse, chirp signal, and Barker code with changing pulse width. It is revealed that choosing the location signal results in the maximum achievable accuracy of fault detection. Using the Barker code provides determination of fault location with an error of 0.2% and signal-to-noise ratio of more than 27 dB.
About the authors
R. I. Shagiev
Institute of Physics, Kazan Federal University
Author for correspondence.
Email: journal-elektrotechnika@mail.ru
Russian Federation, Kazan, 420008
A. V. Karpov
Institute of Physics, Kazan Federal University
Email: journal-elektrotechnika@mail.ru
Russian Federation, Kazan, 420008
S. A. Kalabanov
Institute of Physics, Kazan Federal University
Email: journal-elektrotechnika@mail.ru
Russian Federation, Kazan, 420008
Supplementary files