Limitation of Transient Recovery Voltage When Using Shunt Reactors in 110 – 220 kV Networks


如何引用文章

全文:

开放存取 开放存取
受限制的访问 ##reader.subscriptionAccessGranted##
受限制的访问 订阅存取

详细

In design practice there often arises the problem of assessing the feasibility of installing shunt reactors (SR) when observing conditions of the occurrence of admissible transient recovery voltages at circuit breaker contacts during switching action. A simplified design methodology for this purpose is proposed for calculating the defining parameters of the SR connection circuit, making it possible to define the feasibility of its use in the analyzed circuit.