TCSR Features Facilitating Safe Testing of 500 kV Power Transmission Lines
- Autores: Matinyan A.M.1, Peshkov M.V.1, Karpov V.N.1, Alekseev N.A.1, Pugachenko Z.E.2
-
Afiliações:
- JSC “Scientific Research Center Federal Network Company of the Unified Power System,”
- JSC “Federal Network Company of the Unified Power System PSC,”
- Edição: Volume 51, Nº 2 (2017)
- Páginas: 226-229
- Seção: Power Systems and Electric Networks
- URL: https://journals.rcsi.science/1570-145X/article/view/245732
- DOI: https://doi.org/10.1007/s10749-017-0814-z
- ID: 245732
Citar
Resumo
Reasons are examined for failures of gas-insulated circuit breakers on lines with shunt reactors that provide a level of line compensation close to 100%. It is shown that using a TCSR as a linear reactor makes it possible to eliminate the reason leading to failure of the circuit breaker in line testing.