Assessing the Sensitivity of Relay Protection


Cite item

Full Text

Open Access Open Access
Restricted Access Access granted
Restricted Access Subscription Access

Abstract

An assessment of sensitivity of the measuring elements of relay protection was performed. Based on simple examples of the generator-transformer unit protection from symmetrical short circuits, it was shown that the sensitivity factor is not a sufficiently objective measure of sensitivity of the relay protection. It was suggested to use a more objective measure, which is a characteristic of sensitivity to transient resistance at the fault location (dependence of the transient resistance, at which the protection stops tripping, on the fault location).