Assessing the Sensitivity of Relay Protection
- 作者: Romanov Y.V.1, Voronov P.I.1
-
隶属关系:
- “Relematika” LLC
- 期: 卷 51, 编号 6 (2018)
- 页面: 728-731
- 栏目: Article
- URL: https://journals.rcsi.science/1570-145X/article/view/246056
- DOI: https://doi.org/10.1007/s10749-018-0900-x
- ID: 246056
如何引用文章
详细
An assessment of sensitivity of the measuring elements of relay protection was performed. Based on simple examples of the generator-transformer unit protection from symmetrical short circuits, it was shown that the sensitivity factor is not a sufficiently objective measure of sensitivity of the relay protection. It was suggested to use a more objective measure, which is a characteristic of sensitivity to transient resistance at the fault location (dependence of the transient resistance, at which the protection stops tripping, on the fault location).