Evaporative cooling of air in an adiabatic channel with partially wetted zones


如何引用文章

全文:

开放存取 开放存取
受限制的访问 ##reader.subscriptionAccessGranted##
受限制的访问 订阅存取

详细

The paper deals with the numerical study of heat and mass transfer in the process of direct evaporation air cooling in the laminar flow of forced convection in a channel between two parallel insulated plates with alternating wet and dry zones along the length. The system of Navier–Stokes equations and equations of energy and steam diffusion are being solved in two-dimensional approximation. At the channel inlet, all thermal gas-dynamic parameters are constant over the cross section, and the channel walls are adiabatic. The studies were carried out with varying number of dry zones (n = 0–16), their relative length (s/l = 0–1) and Reynolds number Re = 50–1000 in the flow of dry air (φ0 = 0) with a constant temperature at the inlet (T0 = 30 °C). The main attention is paid to optimization analysis of evaporation cell characteristics. It is shown that an increase in the number of alternating steps leads to an increase in the parameters of thermal and humid efficiency. With an increase in Re number and a decrease in the extent of wet areas, the efficiency parameter reduces.

作者简介

V. Terekhov

Kutateladze Institute of Thermophysics SB RAS; Novosibirsk State Technical University

编辑信件的主要联系方式.
Email: terekhov@itp.nsc.ru
俄罗斯联邦, Novosibirsk; Novosibirsk

M. Gorbachev

Novosibirsk State Technical University

Email: terekhov@itp.nsc.ru
俄罗斯联邦, Novosibirsk

H. Khafaji

Kutateladze Institute of Thermophysics SB RAS; Novosibirsk State Technical University

Email: terekhov@itp.nsc.ru
俄罗斯联邦, Novosibirsk; Novosibirsk

补充文件

附件文件
动作
1. JATS XML

版权所有 © Pleiades Publishing, Ltd., 2016