Permissible Electrical-Field Intensities in the Cast Epoxy Insulation of a 6- to 110-kV Switchgear


Citar

Texto integral

Acesso aberto Acesso aberto
Acesso é fechado Acesso está concedido
Acesso é fechado Somente assinantes

Resumo

The method of choice of the working intensity of the electrical field in the cast epoxy insulation of a 6- to 110-kV switchgear taking into account its dimensions, structure, and basic operational factors is studied. The volt–time characteristics of the electrical strength of the cast epoxy insulation corresponding to a low probability of the breakdown at the different intensity of the partial discharges are analyzed. It is shown that the distribution of the electrical strength of the cast insulation under the short-term and long-term action of the commercial-frequency voltage is well described by the Weibull law and the influence of the dimensions on the electrical strength is specified by the “active” volume of the dielectric—the area where the electricalfield intensity makes up no less than 85% of the maximum in the clearance. The estimation of the permissible field intensities in the cast insulation of a 10- to 35-kV switchgear with various degrees of the field inhomogeneity and intensities of the partial discharges is given.

Sobre autores

V. Varivodov

Moscow Power Engineering Institute

Autor responsável pela correspondência
Email: journal-elektrotechnika@mail.ru
Rússia, Moscow, 111250

D. Kovalev

Moscow Power Engineering Institute

Email: journal-elektrotechnika@mail.ru
Rússia, Moscow, 111250

N. Krupenin

AO NPO VEI Elektroizolyatsiya

Email: journal-elektrotechnika@mail.ru
Rússia, Moscow

S. Khrenov

Moscow Power Engineering Institute

Email: journal-elektrotechnika@mail.ru
Rússia, Moscow, 111250

Arquivos suplementares

Arquivos suplementares
Ação
1. JATS XML

Declaração de direitos autorais © Allerton Press, Inc., 2018