Diagnostics and an on-load operation algorithm of high-speed voltage regulators


Cite item

Full Text

Open Access Open Access
Restricted Access Access granted
Restricted Access Subscription Access

Abstract

Diagnostics methods are considered of single- and three-phase high-speed switching units, such as of the PC and PNOA series, mounted on 35- to 330-kV power transformers. The diagnostics is carried out using a multichannel digital oscilloscope without opening the contactor tank and draining the dielectric liquid from it. Algorithms for automated determination of working capacity of switching devices are presented. It is revealed that the developed algorithms make it possible to shorten the time for preparing and obtaining the oscillograms of currents and automatic processing of measured values, automate the determination of working capacity of switching devices, record the diagnosing results in print, and create a database in digital form.

About the authors

G. M. Mikheev

Cheboksary Branch

Author for correspondence.
Email: journal-elektrotechnika@mail.ru
Russian Federation, Cheboksary

T. G. Ivanova

Cheboksary Branch

Email: journal-elektrotechnika@mail.ru
Russian Federation, Cheboksary

D. I. Konstantinov

Chuvash State University; OOO Proekteleсtroteсhnika

Email: journal-elektrotechnika@mail.ru
Russian Federation, Cheboksary; Shumerlya, Chuvash Republic

A. Kh. Turdiev

Chuvash State University

Email: journal-elektrotechnika@mail.ru
Russian Federation, Cheboksary

Supplementary files

Supplementary Files
Action
1. JATS XML

Copyright (c) 2017 Allerton Press, Inc.