Protection of a Single-Phase Transformer from Interwinding Failure in Windings of Integral Magnetic Transformers


如何引用文章

全文:

开放存取 开放存取
受限制的访问 ##reader.subscriptionAccessGranted##
受限制的访问 订阅存取

详细

A simple means of protection of a powerful single-phase transformer with integral magnetic transformers has been suggested. The protection has a high sensitivity to the interwinding failure and is based on the measurements of unsymmetry of the leakage magnetic fluxes of transformer windings. This magnetic unsymmetry is determined by the difference of electromotive forces of windings of two magnetic transformers placed symmetrically with respect to the symmetry plane of the protected transformer. It has been suggested to produce the magnetic transformers in the form of a single-layer winding with an alternating pitch, which is wound around a textolite round or rectangular body. The length of a magnetic transformer is taken to be equal to the length of a magnetic core, which allows one to provide independence of protection sensitivity on the location of closed turns on the transformer rod. To measure the difference of the emf of magnetic transformers, the circuit of comparison with a responsive element in the form of a TT-40/0.2 or RT1-P/0.15 current relay has been used. Methods to determine a trigger threshold and sensitivity of the protection to interwinding failure as well as to ironwork failure have been suggested.

作者简介

A. Novozhilov

Toraighyrov Pavlodar State University

编辑信件的主要联系方式.
Email: journal-electrotechnika@mail.ru
哈萨克斯坦, Pavlodar

V. Goryunov

Omsk State Technical University

Email: journal-electrotechnika@mail.ru
俄罗斯联邦, Omsk

T. Novozhilov

Omsk State Technical University

Email: journal-electrotechnika@mail.ru
俄罗斯联邦, Omsk

补充文件

附件文件
动作
1. JATS XML

版权所有 © Allerton Press, Inc., 2018