A new PMU based power swing detector to prevent mal-operation of distance relay
- Авторы: Ouadi A.1, Bentarzi H.1, Chafai M.1
- 
							Учреждения: 
							- Signals and Systems Laboratory, IGEE
 
- Выпуск: Том 87, № 10 (2016)
- Страницы: 572-578
- Раздел: Article
- URL: https://journals.rcsi.science/1068-3712/article/view/229687
- DOI: https://doi.org/10.3103/S1068371216100059
- ID: 229687
Цитировать
Аннотация
In conventional transmission line protection, a distance relay is used to provide the primary as well as remote backup protection. The voltage and current phasors measurement needed by the distance relay for determining the impedance may be affected by the power disturbances such as power swing. Consequently, this power swing may cause mal-operation of Zone three distance relays which in turn may affect on the reliability of the whole protective scheme. To mitigate these effects and hence improve the relay reliability, this work proposes a new real-time power swing detector using phasor measurement units for blinding the distance relay only during this transient disturbance. However, this developed detector will not block relay when the power swing accompanied with faults. To validate the present work, the performance of developed enhanced distance relay is tested by signals generated by Simulink/MATLAB simulator under different conditions. The test results show that this proposed scheme provides good discrimination between the transient currents and the fault current which in turn it may contribute in enhancing the reliability of Distance relay.
Ключевые слова
Об авторах
A. Ouadi
Signals and Systems Laboratory, IGEE
														Email: bentarzi_hamid@yahoo.com
				                					                																			                												                	Алжир, 							Boumerdes, 35000						
H. Bentarzi
Signals and Systems Laboratory, IGEE
							Автор, ответственный за переписку.
							Email: bentarzi_hamid@yahoo.com
				                					                																			                												                	Алжир, 							Boumerdes, 35000						
M. Chafai
Signals and Systems Laboratory, IGEE
														Email: bentarzi_hamid@yahoo.com
				                					                																			                												                	Алжир, 							Boumerdes, 35000						
Дополнительные файлы
 
				
			 
						 
					 
						 
						 
						 
									 
  
  
  
  
  Отправить статью по E-mail
			Отправить статью по E-mail  Открытый доступ
		                                Открытый доступ Доступ предоставлен
						Доступ предоставлен Только для подписчиков
		                                		                                        Только для подписчиков
		                                					