Single bubble of an electronegative gas in transformer oil in the presence of an electric field
- Authors: Gadzhiev M.K.1, Tyuftyaev A.S.1, Il’ichev M.V.1
-
Affiliations:
- Joint Institute for High Temperatures
- Issue: Vol 62, No 10 (2017)
- Pages: 1500-1504
- Section: Gases and Liquids
- URL: https://journals.rcsi.science/1063-7842/article/view/200104
- DOI: https://doi.org/10.1134/S1063784217100103
- ID: 200104
Cite item
Abstract
The influence of the electric field on a single air bubble in transformer oil has been studied. It has been shown that, depending on its size, the bubble may initiate breakdown. The sizes of air and sulfur hexafluoride bubbles at which breakdown will not be observed have been estimated based on the condition for the avalanche-to-streamer transition.