Single bubble of an electronegative gas in transformer oil in the presence of an electric field
- Авторы: Gadzhiev M.1, Tyuftyaev A.1, Il’ichev M.1
-
Учреждения:
- Joint Institute for High Temperatures
- Выпуск: Том 62, № 10 (2017)
- Страницы: 1500-1504
- Раздел: Gases and Liquids
- URL: https://journals.rcsi.science/1063-7842/article/view/200104
- DOI: https://doi.org/10.1134/S1063784217100103
- ID: 200104
Цитировать
Аннотация
The influence of the electric field on a single air bubble in transformer oil has been studied. It has been shown that, depending on its size, the bubble may initiate breakdown. The sizes of air and sulfur hexafluoride bubbles at which breakdown will not be observed have been estimated based on the condition for the avalanche-to-streamer transition.