Investigation of Heat Pump Efficiency on Zeotropic Refrigerants R32/R134a and R32/R152a


如何引用文章

全文:

开放存取 开放存取
受限制的访问 ##reader.subscriptionAccessGranted##
受限制的访问 订阅存取

详细

Results of analysis of thermodynamic cycle efficiency with consideration of nonisothermal nature of phase transition indicate that when using the mixture of R32/R152a (30/70%) in the vapor compression heat pumps, the coefficient of performance is up to 4% higher in comparison with R32/R134a (30/70%). The study shows that in cycles with two-stage compression the coefficient of performance increases by 6.5% as compared to the single-stage process. The value of exergic efficiency of the single-stage cycle is equal to 0.47 for zeotropic mixture of R32/R152a (30/70%), and it is equal to 0.45 for the R32/R134a (30/70%) mixture. Data obtained for the zeotropic mixtures are as effective as those obtained for refrigerant R134a.

作者简介

N. Mezentseva

Kutateladze Institute of Thermophysics, Siberian Branch

编辑信件的主要联系方式.
Email: mnn@itp.nsc.ru
俄罗斯联邦, pr. Akad. Lavrent’eva 1, Novosibirsk, 630090