Investigation of Heat Pump Efficiency on Zeotropic Refrigerants R32/R134a and R32/R152a


Citar

Texto integral

Acesso aberto Acesso aberto
Acesso é fechado Acesso está concedido
Acesso é fechado Somente assinantes

Resumo

Results of analysis of thermodynamic cycle efficiency with consideration of nonisothermal nature of phase transition indicate that when using the mixture of R32/R152a (30/70%) in the vapor compression heat pumps, the coefficient of performance is up to 4% higher in comparison with R32/R134a (30/70%). The study shows that in cycles with two-stage compression the coefficient of performance increases by 6.5% as compared to the single-stage process. The value of exergic efficiency of the single-stage cycle is equal to 0.47 for zeotropic mixture of R32/R152a (30/70%), and it is equal to 0.45 for the R32/R134a (30/70%) mixture. Data obtained for the zeotropic mixtures are as effective as those obtained for refrigerant R134a.

Sobre autores

N. Mezentseva

Kutateladze Institute of Thermophysics, Siberian Branch

Autor responsável pela correspondência
Email: mnn@itp.nsc.ru
Rússia, pr. Akad. Lavrent’eva 1, Novosibirsk, 630090

I. Mezentsev

Kutateladze Institute of Thermophysics, Siberian Branch

Email: mnn@itp.nsc.ru
Rússia, pr. Akad. Lavrent’eva 1, Novosibirsk, 630090

Arquivos suplementares

Arquivos suplementares
Ação
1. JATS XML

Declaração de direitos autorais © Pleiades Publishing, Ltd., 2018