Joint Regulation of Power Flow and Short Circuit Current Limitations with the Aid of a Phase-Shifting Transformer
- Authors: Brilinskii A.S.1, Evdokunin G.A.2, Mingazov R.I.1, Petrov N.N.1, Chudnyi V.S.2
-
Affiliations:
- Scientific and Technical Center of the Unified Power System
- Peter the Great St. Petersburg Polytechnical University
- Issue: Vol 51, No 5 (2018)
- Pages: 584-592
- Section: Power Systems and Electric Networks
- URL: https://journals.rcsi.science/1570-145X/article/view/245976
- DOI: https://doi.org/10.1007/s10749-018-0878-4
- ID: 245976
Cite item
Abstract
The efficiency of installation of the phase-shifting transformer (PST) in the power supply system of St. Petersburg and the Leningrad Oblast’ is examined, making it possible to execute power flow management within the specified range and limit short-circuit currents to values that do not exceed the breaking capacity of the switching equipment. Its optimal parameters were found, based on analysis of various PST operating modes. Proceeding from this, design calculation of the magnetic core and transformer windings was performed.
About the authors
A. S. Brilinskii
Scientific and Technical Center of the Unified Power System
Author for correspondence.
Email: brilinskiy_a@ntcees.ru
Russian Federation, St. Petersburg
G. A. Evdokunin
Peter the Great St. Petersburg Polytechnical University
Email: brilinskiy_a@ntcees.ru
Russian Federation, St. Petersburg
R. I. Mingazov
Scientific and Technical Center of the Unified Power System
Email: brilinskiy_a@ntcees.ru
Russian Federation, St. Petersburg
N. N. Petrov
Scientific and Technical Center of the Unified Power System
Email: brilinskiy_a@ntcees.ru
Russian Federation, St. Petersburg
V. S. Chudnyi
Peter the Great St. Petersburg Polytechnical University
Email: brilinskiy_a@ntcees.ru
Russian Federation, St. Petersburg