TCSR Features Ensuring the Prevention of Voltage Resonance During Power Transmission Line Single Phase Auto-Reclosing
- Authors: Matinyan A.M.1, Peshkov M.V.1, Karpov V.N.1, Alekseev N.A.1
-
Affiliations:
- JSC “R&D Center at Federal Grid Company of Unified Energy System”
- Issue: Vol 51, No 1 (2017)
- Pages: 114-118
- Section: Article
- URL: https://journals.rcsi.science/1570-145X/article/view/245638
- DOI: https://doi.org/10.1007/s10749-017-0795-y
- ID: 245638
Cite item
Abstract
A description is provided of the operating mode of a line equipped with a thyristor-controlled shunt reactor (TCSR) with split valve-side windings, in a single-phase ARC (SPAR) cycle after arc quenching. It is shown that a TCSR is sufficiently fast to prevent the development of resonant overvoltages in the open-phase operating mode of a power transmission line (PTL).