An Adaptive Fault-Location Method for a Power-Transmission Line Using Pulse Registration on a High-Frequency Wave Path
- Авторлар: Kulikov A.L.1, Anan’ev V.V.1
-
Мекемелер:
- Nizhny Novgorod State Technical University
- Шығарылым: Том 89, № 1 (2018)
- Беттер: 26-31
- Бөлім: Article
- URL: https://journals.rcsi.science/1068-3712/article/view/231381
- DOI: https://doi.org/10.3103/S1068371218010108
- ID: 231381
Дәйексөз келтіру
Аннотация
An adaptive traveling-wave method to improve the accuracy of fault location has been developed. The suggested method can compensate for an error of the two-sided method caused by the dispersive nature of a phase wire along which a high-frequency electromagnetic pulse propagates from the point of the fault. The error in fault location has been determined depending on the means of registration of a high-frequency signal. Some recommendations on connection of facilities to register electromagnetic pulses used in the devices of traveling-wave fault location have been provided. The suggested method allows one to substantially reduce errors of estimation of distance to the point of a fault and is less affected by external factors. The developed method can be applied in both in existing and future devices for fault location.