On optimization of the insulation of high-voltage coaxial bushing


如何引用文章

全文:

开放存取 开放存取
受限制的访问 ##reader.subscriptionAccessGranted##
受限制的访问 订阅存取

详细

This paper considers ways to improve the electric strength of a high-voltage bushing by decreasing the maximum electric intensity. For a coaxial cylindrical bushing with radii r0 and rm > r0, which result in an insulation gap (rmr0) with permittivity ε0, this problem is solved with the use of an additional layer of insulation. This layer, with permittivity ε > ε0, is limited by radii r0 and rε < rm. A simple algorithm to calculate an optimal thickness of this layer was obtained; the algorithm minimizes the maximum intensity as a function of radii r0 and rm and relative permittivity ε/ε0 > 1.582. The algorithm is also transformed into an algorithm of synthesis of the noted layer thickness providing minimum intensity Em. The optimal relative values of all the dimensions of a high-voltage bushing as a function of the layer permittivity and level of reduction in the intensity Em are given in a form that is convenient for practical use.