The double-ended travelling wave method of determination of location of a fault in electrical networks has significant errors due to changes in the propagation velocity of electromagnetic waves. We have developed a travelling wave method of improving the accuracy of location of a fault determination in power transmission lines that is based on navigation algorithms. The method is applicable to lines with branches. The distance to fault determination for the developed method is up to twice as accurate as the double-ended travelling wave location of a fault method. The accuracy of the developed method is less influenced by external factors (change of sag, soil resistance, the instantaneous value of the current at the fault time) than is the accuracy of the double-ended travelling wave location of a fault method. The proposed method allows reducing the errors in determining distance to the location of a fault, and its accuracy is less affected by external factors. The developed method can be incorporated into existing and prospective devices based on travelling wave methods of location of a fault determination.

作者简介

A. Kulikov

Department of Electrical Power Engineering, Electricity Supply, and Power Electronics

编辑信件的主要联系方式.
Email: journal-elektrotechnika@mail.ru
俄罗斯联邦, ul. Minina 24, Nizhni Novgorod, 603950

V. Anan’ev

Department of Electrical Power Engineering, Electricity Supply, and Power Electronics

Email: journal-elektrotechnika@mail.ru
俄罗斯联邦, ul. Minina 24, Nizhni Novgorod, 603950

补充文件

附件文件
动作
1. JATS XML

版权所有 © Allerton Press, Inc., 2016