Technique and Calculation Results of Currents and Voltages in the Circuits of the Measuring Element of the Protection Device of the Transmission Line Based on the Control of Transient Processes


Cite item

Full Text

Open Access Open Access
Restricted Access Access granted
Restricted Access Subscription Access

Abstract

The specifics of generation of the signals of current and voltage in the circuits of a directional element of wave relay protection during short circuit (SC) in overhead power transmission lines are considered. The computing method of transient processes in the protection circuits, including frequency filters, that attenuate the parameters of currents and voltages of the mode taking into account the higher harmonic components and probable deviations of the frequency of transmission line from the rated value is presented. It is revealed that it is advisable to implement the measuring circuits of the directional elements of wave relay protection with the three-section filter attenuating the frequencies from 45 to 55 Hz and the low pass filter with cutoff frequency that does not exceed 1 kHz.

About the authors

V. F. Lachugin

Krzhizhanovsky Power Engineering Institute (OAO ENIN)

Author for correspondence.
Email: lachugin@eninnet.ru
Russian Federation, Moscow, 119991

A. L. Kulikov

Alekseev State Technical University (NNSTU)

Email: lachugin@eninnet.ru
Russian Federation, Nizhny Novgorod, 603950

P. S. Platonov

Krzhizhanovsky Power Engineering Institute (OAO ENIN)

Email: lachugin@eninnet.ru
Russian Federation, Moscow, 119991

V. Yu. Vucolov

Alekseev State Technical University (NNSTU)

Email: lachugin@eninnet.ru
Russian Federation, Nizhny Novgorod, 603950

Supplementary files

Supplementary Files
Action
1. JATS XML

Copyright (c) 2017 Pleiades Publishing, Inc.