Development and Investigation of a Two-Phase Loop Thermosiphon with a Flat Evaporator at Different Slope Angles
- 作者: Dmitrin V.I.1, Maydanik Y.F.1
-
隶属关系:
- Institute of Thermal Physics, Ural Branch
- 期: 卷 56, 编号 1 (2018)
- 页面: 92-97
- 栏目: Heat and Mass Transfer and Physical Gasdynamics
- URL: https://journals.rcsi.science/0018-151X/article/view/157465
- DOI: https://doi.org/10.1134/S0018151X18010054
- ID: 157465
如何引用文章
详细
We present the results of the development and experimental studies of a two-phase loop thermosiphon with a flat evaporator and ethanol as the working fluid. We investigate the thermal characteristics of the device within the temperature range of 20–80°C under the heat loads of 10–120 W, a filling ratio of 40%, and slope angles within the range of 0°–90°. The device is functional at all of the studied slope angles. The maximum heat load of 120 W was reached at the slope angle of 90°. Here, the average temperature of the evaporator surface was within 70°C and the maximum thermal resistance was equal to 0.41°C/W.
作者简介
V. Dmitrin
Institute of Thermal Physics, Ural Branch
Email: maidanik@yandex.ru
俄罗斯联邦, Ekaterinburg, 620016
Yu. Maydanik
Institute of Thermal Physics, Ural Branch
编辑信件的主要联系方式.
Email: maidanik@yandex.ru
俄罗斯联邦, Ekaterinburg, 620016
补充文件