Heat Transfer in a Water Flow in Tubes with Ribbed Twisted Tape Inserts


Cite item

Full Text

Open Access Open Access
Restricted Access Access granted
Restricted Access Subscription Access

Abstract

The results of an experimental study of heat transfer in a water flow in a channel with a twisted tape insert with discrete ribs installed at an angle to the tape axis are presented. The experiments were performed in a straight smooth tube with an inner diameter of 10 mm. The tape inserts had a twist ratio of 2.5, 3, or 4 with a 180° rotation; the rib height ranged from 0.5 to 1.5 mm, the rib pitch was from 40 to 120 mm, and the rib angle was from 40 to 50° to the tape axis. The results of experiments in the mentioned range of geometries suggest that the ribbed tape inserts increase heat transfer by a maximum of 40% as compared with that in tubes with a twisted tape without ribs. The generalized correlation is given for the prediction of heat transfer in a Reynolds number range Re = 104‒2 × 105.