The existed combined power and cooling cycle operates with ammonia–water mixture as working fluid having low cooling due to the vapor at the inlet of evaporator. It also demands high ammonia concentration at turbine inlet to get cooling and suitable only at low sink temperature (10–12°C). A new cooling cogeneration cycle has been proposed and solved to generate more cooling with adequate power generation from single source of heat with two options in working fluids i.e. ammonia–water mixture and LiBr–water mixture. The results show that an increase in cycle maximum temperature is only supporting the power but not the cooling. A suitable range for separator temperature has been developed and optimized to maximize the total output. From this study, the resulted specific power, specific cooling, cycle power efficiency, cycle coefficient of performance (COP) and cycle energy utilization factor (EUF), plant EUF, and specific area of solar collector are 0.008 kW/m2, 0.11 kW/m2, 2%, 0.28, 0.3, 0.13 and 8 m2/kW for ammonia–water cycle and 0.04 kW/m2, 0.3 kW/m2, 9.5%, 0.7, 0.8, 0.37 and 3 m2/kW for LiBr–water mixture plant respectively.