Determination of the Dielectric Characteristics of Electric Equipment Insulation in the Presence of Utility-Frequency Interference Currents


Цитировать

Полный текст

Открытый доступ Открытый доступ
Доступ закрыт Доступ предоставлен
Доступ закрыт Только для подписчиков

Аннотация

The operation of modern microprocessor insulation analyzers operating at the utility frequency and implementing the two measurements method (computational method) which are widely used to assess the condition of insulation in electric equipment is analyzed. The expressions and computational results are presented for the errors appearing in tanä due to the voltage setting difference between the first and second measurements and the action of the utility-frequency interference currents on the source of the testing voltage. It is shown that the two measurements method gives acceptable errors if the voltage difference between the first and second measurements does not exceed 0.2 – 0.5%. It is noted that the level of the additional errors of the insulation analyzers using the two measurements method is comparable to the error of simple analyzers of the type Tangens-2000 operating on a non-utility frequency and having significant additional errors in the presence of utility-frequency interference currents in the distribution devices.

Об авторах

G. Shinkarenko

Donbass Electric Power System

Автор, ответственный за переписку.
Email: gleb_shin@mail.ru
Украина, Artemovsk, Donetsk oblast’


© Springer Science+Business Media New York, 2016

Данный сайт использует cookie-файлы

Продолжая использовать наш сайт, вы даете согласие на обработку файлов cookie, которые обеспечивают правильную работу сайта.

О куки-файлах