Use of Backup Distance Protection on a Block Transformer
- Autores: Frolova E.I.1, Osintsev A.A.1
-
Afiliações:
- Novosibirsk State Technical University
- Edição: Volume 50, Nº 2 (2016)
- Páginas: 220-223
- Seção: Article
- URL: https://journals.rcsi.science/1570-145X/article/view/245170
- DOI: https://doi.org/10.1007/s10749-016-0687-6
- ID: 245170
Citar
Resumo
The use of the conventional approach to picking set points and the application of classic algorithms for distance protection in a number of cases do not give the required sensitivity, which the computational results presented in this paper clearly show. An unconventional approach to solving this problem is proposed: the simultaneous use of several independent measuring elements in the distance protection step.